Guidance FAQs

How to PAT Test – Free YouTube videos

You can watch our how guided videos on You Tube to find out what is involved in PAT Testing and how to PAT Test.  Our You Tube channel has various chapters from the introduction, showing you how to work the PAT Tester, and explaining why we do PAT Testing. Through to what to do if a piece of equipment fails the test.

https://www.youtube.com/@ParkerBellCoUk-PAT/videos

There is more information available – especially if you need help because equipment has failed unexpectedly. The chapters are clearly labelled and if you can’t find the help you need, you can call us on 01392 364933 9am – 5pm, Monday to Friday (Excl. Weekends &  Bank Holidays)

The videos compliments our already successful free online PAT Testing course:

https://www.onlinepattestingcourse.co.uk

Any competent person can do PAT Testing. You just need to know How to PAT Test and how to keep records. The videos are particularly helpful for Charity Shops, Repair Cafes, Maintenance people and tradespeople needing specific PAT Testing guidance.

The PB500VX is our latest machine which is IET 5th Edition and British Standard compliant.

For technical support and guidance. Call us on 01392 364933 or email sales@parker-bell.co.uk

 

Quick Start Guide PB500VX

Download our Free Quick Start Guide now:

PB500VX Quick Start Guide MAR23

Other guides are available here:

Riso Test Fail

Long Lead Test Jan 23

PB500VX Quick Start Guide

PAT Testing sequence

  1. Risk Assessment to determine frequency of testing.
  2. Full visual Inspection which will determine the Class of the equipment.
  3. PAT Test
  4. Label the equipment & complete the record/log.
  5. Functional Test

How to switch on/off & useful tips:

  • Switch on: press the Class I & Class II buttons together until you hear two beeps.
  • Switch off: press the Class I & Class II buttons together and hold.
  • Remove batteries after use. Leakage can damage the printed circuit board.
  • Apply a green pass label to the equipment itself, rather than the plug, and use a cable tag for a lead.

 

 Where to find more information

The Parker Bell website www.parker-bell.co.uk has lots of useful information. Free PAT Tester training can be found at www.onlinepattestingcourse.co.uk. You can call us and get technical support Monday to Friday 9am until 5pm on 01392 364933 or by emailing sales@parker-bell.co.uk.

 

Visual Inspection

  • Is the plug damaged in any way?
  • Check the plug is suitable?
  • Ensure the flexible lead is secure at the anchorage grip.
  • Has a non-moulded plug been correctly wired?
  • Are the wires securely attached to the correct terminals?
  • Any loose strands of wire?
  • Does the fuse have the correct fuse rating and is it secure?
  • Remove any paper wiring diagram that might have been placed over the pins.
  • New plugs must have a partial sleeve on the live and neutral pins.
  • Straighten any tightly bent cable.
  • Make sure leads haven’t been damaged.
  • Extension leads shouldbe Class I.
  • Remember, extension leads should only be used on a temporary basis. Install a new socket-outlet nearer the equipment.
  • Check the equipment is not damaged in any way.

 

PASS

Update the visual inspection section of your register/log. You should now know the Class of the equipment you are testing.

 

FAIL

Minor faults can be rectified if you know how to, e.g., changing an incorrect fuse or broken plug.  You can then proceed to test.

 

Other repairs will need to be carried out by an electrician or competent person and your action recorded in your register/log.

 

Using the PB500VX

 

Insulation Resistance

 

The PB500VX displays the Insulation Resistance voltage of a test when initiated as either:

 

representing a 500 volts Test

 

representing a 250 volts  Test

The machine is initially set to 500 volts. You can change the value to 250 volts during the test of surge-protected equipment. It will revert to 500 volts for subsequent tests. For further information see the Set Up Guide on page 12.

 

Leakage Limits

 

The PB500VX default setting displays the maximum reading in mA for both Class I and Class II as shown in the table below:

 

Equipment IET 5th Edition Values
Class I 5mA
Class II 5mA

 

Class I Test

Only carry out the PAT test once a full visual inspection has been completed and passed

 

Class I equipment is earthed and has 3 wires in the plug. Earth, Live and Neutral.

 

  1. Switch on the PB500VX.
  2. Insert the round jack of the earth test lead into the top of the PB500VX.
  3. Using the probe or crocodile clip connect to an external metal earth point on the equipment.
  4. Inset the plug of the equipment into the front socket of the PB500VX.
  5. Make sure the equipment switch is in the ON position.
  6. Press the Class I
  7. If Long Lead Test? is displayed, a calculation is required. Go to page 10.
  8. If Lo Load is displayed on the screen, check the equipment is switched on. If there is no on/off switch press the Class I button again.

 

PASS

Update the appropriate section of your register/log.

 

FAIL

No Earth – See Page 12.

Long Lead Test -Page 10.

X Riso – See X Riso Fail Guide – Page 12.

X Ileak – See X Ileak Fail Guide – Page 12.

 

Class II Test

Only carry out the PAT test once a full visual inspection has been completed and passed

Class II equipment has two wires in the plug: live and neutral.  This symbol is often displayed on the manufacturer’s label.

 

  1. Switch on the PB500VX.
  2. Inset the plug of the equipment into the front socket of the PB500VX.
  3. Make sure the equipment switch is in the ON position.
  4. Press the Class II
  5. If Lo Load is displayed on the screen. Check the equipment is switched on. If there is no on/off switch, press the Class II button again.

 

PASS

Update the appropriate section of your register/log.

 

FAIL

X Riso – See X Riso Fail Guide – Page 12.

X Ileak – See X Ileak Fail Guide – Page 12.

 

Class II FE Test

Only carry out the PAT test once a full visual inspection has been completed and passed.

 

Class II FE equipment has three wires in the plug; a functional Earth, Live and Neutral.  This symbol is often displayed on the manufacturer’s label.

 

This equipment is tested as a Class II because the earth wire is not protective. See Page 5.

 

PASS

Update the appropriate section of your register/log.

 

FAIL

X Riso – See X Riso Fail Guide – Page 12.

X Ileak – See X Ileak Fail Guide – Page 12.

 

IEC Lead Testing

Only carry out the PAT test once a full visual inspection has been completed and passed.

 

IEC Leads should be recorded and labelled separately.

 

  1. Switch on the PB500VX.
  2. Insert the socket of the supplied IEC lead into the IEC plug located on the top of the PAT Tester.
  3. Insert the plug of the IEC lead into the socket of the PB500VX.
  4. Press the Cord
  5. If Long Lead Test? is displayed, a calculation is required. Go to page 10.

 

PASS

Update the appropriate section of your register/log.

 

FAIL

No Earth – See Page 12.

Long Lead Test – Page 10.

X Riso – See X Riso Fail Guide – Page 12.

Short/Open/Cross – See Polarity Fail Guide – Page 12.

  

Extension Lead Testing

Only carry out the PAT test once a full visual inspection has been completed and passed.

 

Extension leads should be recorded separately.

 

  1. Switch on the PB500VX
  2. Insert the socket of the supplied IEC lead into the IEC plug located on the top of the PAT Tester.
  3. Insert the plug of the IEC lead into the first or only socket of the extension lead and insert the plug of the extension lead into the socket of the PB500VX.
  4. Press the Cord
  5. Repeat the test for every socket.
  6. If Long Lead Test? is displayed, a calculation is required. Go to page 10.
  7. All sockets must be tested. If one fails, the lead must be failed.

 

PASS

Update appropriate section of your register/log.

 

FAIL

No Earth – See Page 12.

Long Lead Test – Page 10.

X Riso – See X Riso Fail Guide – Page 12.

Short/Open/Cross – See Polarity Fail Guide – Page 12.

 

Mains Power Outlet/Socket Test

Only carry out the PAT test once a full visual inspection has been completed and passed.

  1. Switch on the PB500VX.
  2. Insert the socket of the supplied IEC lead into the IEC plug located on the top of the PAT Tester.
  3. Insert the plug of the IEC Lead into the mains power outlet.
  4. Switch the socket on.

 

PASS

Update the appropriate section of your register/log.

 

FAIL

LN / LE / NE   X  Fail – shows incorrect wiring. Do not use the socket and contact an electrician.

 

 

Long Leads Tests.

*If the equipment you are testing does not have a long lead you should seek a better earth connection.

If the PB500VX displays Long Lead Test? the display will pause for approx. 9 seconds before continuing the test sequence. You will see an X displayed next to Rpe and an overall Fail.

  1. Perform the calculation on page 11 to determine if the resistance reading is within maximum tolerance.
  2. If the resistance reading is acceptable repeat the test and press the Cord button again when Long Lead Test?
  3. A ü will now appear next to

 

Note. You must not press the cord button for a second time unless you are certain you have carried out the calculation on page 11, otherwise you may have a false positive outcome.

 

Long Lead Earth Resistance Calculation

 

Cable CSA Ohms per metre
0.5mm2 0.039Ω
0.75mm2 0.026 Ω
1.0mm2 0.0195 Ω
1.25mm2 0.0156 Ω
1.5mm2 0.0133 Ω
2.5mm2 0.008 Ω
4.00mm2 0.005 Ω

 

The above table shows the ohms (Ω) per metre value for the CSA (cross sectional area) of the lead.

 

The maximum figure is calculated by multiplying the length of the lead in metres by the Ohms per meter value for the lead’s CSA plus 0.1 ohm. The CSA is stamped on the lead.

Lead length
0.1 Ω
Calculation result
Ohms per metre

 

Remove or repair the equipment if the figure shown on the PC500VX is above the calculated figure.

 

 No Earth – probable causes

  1. Have you connected the earth test lead?
  2. The earth test lead probe/clip is not touching an external earth point. Retry on other metal parts.
  3. The earth wire is broken. The equipment should be removed from use.
  4. If using the IEC lead, is it fully inserted into the plug at the top of the PB500VX?

 

X Riso Fail Guide

If your surge-protected equipment/extension lead has failed the 500 volts Riso insulation resistance test, the setting can be changed to 250 volts by repeating the test as follows.

 

Press and hold down the Cord button for 5 seconds until a beep is heard. A small triangular symbol with an exclamation mark will briefly flash at the bottom of the screen. Release the button and the Riso test will be done at 250 volts. The Riso test will then revert to 500 volts for any subsequent tests.

Remove or repair equipment if it still fails.

X Ileak Fail Guide

The maximum value for Class I, Class II and Class IIFE is

5.0 mA. Any reading above is a fail.

 

Polarity Fail Guide

If your equipment/lead/socket is incorrectly wired, the screen will indicate the reason such as short, open (not connected) or crossed.

 

Set Up Guide

The PB500VX Set Up Menu allows:

  1. The resistance of the earth Rpe test to be set as either 0.1 Ω, 0.2Ω or 0.3Ω.
  2. The default voltage of the insulation resistance Riso test to be changed from 500 vdc to 250 vdc.
  3. The ILeak resistance test, which is set in accordance with the IET 5th Edition Code of Practice, to be changed to the British Standard BS EN 50699 & BS EN 5067800.

Entering the Set-Up Menu:

Press and hold the Class II and the Cord buttons at the same time until the SETUP menu displays.

  1. To change the resistance of the earth Rpe, press the Class I button.
  2. To change the voltage of the insulation resistance Riso, press the Class II button.
  3. To change the ILeak resistance test from the IET standard to the British Standard, press the Cord button. Wait until the symbols Rpe and Riso re-appear.

Saving and Exiting the Set-Up Menu.

To save and exit press the Class II and Cord buttons together. If this is not done the PB500VX will remain in the Set Up menu mode.

 

Can Charity Shops PAT Test

Yes. Charity Shops can sell used electrical equipment. Follow these steps:

  1. Get PAT Tester training. You can do this for free at www.onlinepattestingcourse.co.uk
  2. Get the right equipment to PAT Test. The PB500V is exactly the kind of machine the HSE recommends for competent PAT Testers
  3. Check the electrical item hasn’t been recalled by the manufacturer. You can do this here electrical safety first 
  4. Ensure it is British Kite marked and that it meets British standards  
  5. Do a full visual inspection and determine the Class of the equipment
  6. PAT Test the equipment
  7. Make sure the equipment works properly. (functional test)
  8. Label the equipment as safe.

You PAT Test electrical equipment for resale in the same way as you PAT Test anywhere else. The only additional factors are ensuring that the item you are testing has not been recalled by the manufacturer and ensuring that a wiring diagram is included. You should also check if there are any specific trading standards affecting your local area. You should be able to do this on the county council website.

Our Charity kit is ideal for repair cafe’s and charity shops. It includes everything you need to get started. If you would like to know more about what is included with the kit, please look here 

Do I need to pat test every year?

Not necessarily, there is no mandate saying you must pat test every year. You should do a risk assessment to determine the frequency of PAT Testing.

Some items such as IT equipment in an office with a single user and is rarely moved may only need to be tested every 4 years. While an electric drill used daily may need to be tested every three months. It is ok to have different schedules of testing according to risk and therefore it is ideal to take your PAT Testing responsibilities in house.

My Class I or II equipment has failed the ILeak Test.

The IET 5th Edition has updated its guidance regarding the maximum Pass value for the touch current ILeak test. Please see the diagram below:

This means that if your equipment passes the visual inspection and all other tests, providing the ILeak fail is equal to or lower than 5.0 mA  the equipment can be passed.

What is the correct PAT Testing equipment?

The correct equipment is a Pass / Fail PAT Tester such as the PB500V. A machine which provides a Pass / Fail outcome after carrying out the test.

You can read more about this in the free HSE (Health and safety executive) publication hsg107 Maintaining Portable Electrical Equipment dated 24th August 2015 para 50 refers

How often should I pat test?

The responsible person should complete a risk assessment to determine the frequency of PAT Testing for your business. The following factors should be considered when deciding the frequency.

  • Type of industry
  • Type of equipment
  • How often equipment is used / moved
  • Who uses the equipment
  • Age and condition of the equipment
  • Any environmental factors
  • Is the equipment in a rental property
  • Are any local rules / regulations applicable to your industry

This list is not exhaustive. Please assess according to your own business specifics. Low risk equipment such as desktop PCs are typically considered low risk items if they are rarely moved, without multiple users. Whereas electrical equipment using water, equipment used by multiple users, or easily dropped is considered high risk.

If you would like to discuss the best way to conduct your risk assessment, please feel free to call out technical team on 01392 364933 or email your question to sales@parker-bell.co.uk

Contact Us